18-509 : Maintenance of GCE.
- Owners/users are responsible for maintenance of the GCE.
- Grease traps should be cleaned once every two weeks, or sometimes more often, if the combined depth of FOG and solids exceed fifty percent (50%) of the trap.
- Grease Interceptors shall be pumped when the layer of FOG and settled solids combined reaches twenty five percent (25%) of the tank depth.
- When grease interceptors are pumped, the entire contents, FOG layer, settled solids and water shall be fully removed. No water may be returned to the tank.
- Interceptors shall be inspected for deterioration and damage by the waste grease hauler each time the unit is cleaned.
- Deteriorated or damaged tanks shall be repaired or replaced within sixty (60) days of notice of such conditions. (Ord. #527, Feb. 2019)